Doubly Reinforced Concrete Beam — Worked Example with Non-Yielding Compression Steel

By Michael Flynn, PE · water resources & dam safety engineer ·

Architecture fixes a 12 × 20 in beam that must carry Mu = 260 kip-ft. As a singly reinforced section it falls just short of the ACI 318-19 tension-controlled limit, so adding tension steel only makes it worse. Two #7 bars in the top fix it, but they never reach yield, so the textbook "assume f′s = fy" shortcut overstates their contribution.

The beam

Sectionb = 12 in, h = 20 in (depth fixed by the ceiling), rectangular
Materialsf′c = 4,000 psi (β1 = 0.85), Grade 60, 1.5 in clear cover, #3 stirrups, ¾-in aggregate
DemandMu = 260 kip-ft (positive moment)

RC beam tool: bw 12, h 20, aggregate 0.75, 4-#9 bottom, then add 2-#7 compression bars, Mu 260.

Open the RC beam calculator →
Step 1 · The singly reinforced limit

What the section can carry while tension-controlled

dt = 20 − 1.5 − 0.375 − 1.128/2 = 17.56 in (one layer of #9)
At εt = 0.00507: c = 0.003 × 17.56/0.00807 = 6.53 in → a = 0.85c = 5.55 in
As,max = 0.85 × 4 × 12 × 5.55/60 = 3.77 in²
φMn,max = 0.9 × 3.77 × 60 × (17.56 − 5.55/2)/12 = 251 kip-ft < 260
Singly reinforcedεtφφMn (kip-ft)ACI 318-19 §9.3.3.1
3-#9 (3.00 in²)0.00720.900207.3OK, but too weak
4-#9 (4.00 in²)0.00460.862252.0Not tension-controlled — not permitted
Under ACI 318-14 this beam would have passed… almost. The old limit (εt ≥ 0.004, with φ interpolated from 0.005) allowed 4-#9, but φMn ≈ 254 kip-ft still misses 260. Under 318-19 more steel is not an option at all: beams must be tension-controlled.
Step 2 · Add compression steel

Try 4-#9 bottom and 2-#7 top

As = 4.00 in²  ·  A′s = 1.20 in²  ·  d′ = 1.5 + 0.375 + 0.875/2 = 2.31 in
Clear spacing of 4-#9 in 12 in: (12 − 2 × 1.875 − 4 × 1.128)/3 = 1.25 in ≥ max(1 in, db = 1.128, 4/3 × 0.75 = 1.0) ✓
Step 3 · Assume the compression steel yields

The textbook first trial — and why it fails

0.85(4)(12)a = 4.00(60) − 1.20(60 − 3.4) → a = 172.1/40.8 = 4.22 in, c = 4.96 in
ε′s = 0.003(4.96 − 2.31)/4.96 = 0.00160 < εy = 0.00207 → assumption wrong
Step 4 · Strain compatibility

Solve for c with f′s = Esε′s

40.8(0.85c) + 1.20[87(c − 2.31)/c − 3.4] = 240  (f′s in ksi, 87 = Es × 0.003)
Solving: c = 5.33 in, a = 4.53 in
f′s = 87(5.33 − 2.31)/5.33 = 49.3 ksi (elastic)  ·  Cc = 40.8 × 4.53 = 184.8 kip  ·  Cs = 1.20(49.3 − 3.4) = 55.1 kip
εt = 0.003(17.56 − 5.33)/5.33 = 0.0069 ≥ 0.00507 → tension-controlled, φ = 0.90
Mn = 184.8(17.56 − 4.53/2) + 55.1(17.56 − 2.31) = 2,827 + 840 = 3,667 kip-in = 305.6 kip-ft
φMn = 275.1 kip-ft ≥ 260 ✓ (0.95)

The compression bars carry 55 kip instead of the 68 kip the yield assumption would give them. Here the yield assumption would overstate Mn by only 0.8% (307.9 vs 305.6 kip-ft), but it also puts c and εt in the wrong place, and in shallower beams or with larger d′ the error grows quickly.

Step 5 · Compare compression bar sizes

More top steel, diminishing returns

Top barsc (in)f′s (ksi)εtφMn (kip-ft)
none6.92—0.0046252.0 (φ = 0.862)
2-#65.6752.50.0063273.2
2-#75.3349.30.0069275.1
2-#85.0045.60.0075276.6

Even 2-#6 works. Compression steel mostly buys ductility (it moves the beam into the tension-controlled zone); the moment gain beyond that is small because the lever arm hardly changes. 2-#7 is chosen to give a little margin and stiffer stirrup corners.

Tie the top bars. §9.7.6.4: compression bars must be enclosed by ties or closed stirrups at no more than 16 bar diameters (14 in for #7) or 48 tie diameters (18 in for #3) — closed #3 stirrups at the shear spacing usually satisfy this.

Tools used in this example

RC beam design (ACI 318-19). Guide: How to design a reinforced concrete beam. Related: RC T-beam floor beam.

Frequently asked questions

When do you need compression reinforcement in a beam?

When the section is too shallow to develop Mu while staying tension-controlled. Under ACI 318-19 the tension steel must reach εt ≥ εty + 0.003 (0.00507 for Grade 60). Compression bars carry part of the compression force, which raises the neutral axis, increases εt and lets the section reach φ = 0.90 again.

How do you know if compression steel yields?

Compute its strain from the neutral axis: ε′s = 0.003(c − d′)/c. It yields if ε′s ≥ fy/Es = 0.00207. Shallow beams, small c and a large d′ all keep the compression bars elastic. In this example ε′s = 0.0017, so f′s = 49.3 ksi.

Why does adding tension steel not help here?

More tension steel deepens the compression block and lowers εt, which drops φ below 0.90. For this beam the largest tension-controlled singly reinforced capacity is 251 kip-ft, which is less than 260, no matter how the steel is chosen.

Do compression bars need ties?

Yes. ACI 318-19 §9.7.6.4 requires compression reinforcement in beams to be enclosed by ties or stirrups, sized and spaced like column ties (§25.7.2), so the bars cannot buckle outward.