All tools Print with PE stamp box Designed for sealed engineering submittals — print drops PE stamp + signature block at the end.

Motor Full-Load Amps (FLA)

Calculate full-load current of a three-phase or single-phase induction motor from horsepower, line voltage, motor efficiency, and power factor. NEC 430.250 tabulated FLA shown for comparison — use the table value for branch-circuit design, not the calculated value.

hp
% (NEMA Premium ≥ 93–95% for 50–200 hp)
— (typical 0.80–0.90 for induction)
A
A (for circuit sizing)
A (~6× FLA, NEMA design B)
A (TM circuit breaker, 250%)

Defaults: 50 hp, 460V three-phase, 93% efficiency, 0.86 PF — typical industrial motor. NEC 430.250 tabulated values are conservative — use them for OCPD and conductor sizing per NEC 430.6(A)(1).

Three-phase FLA from hp:
$$ \text{FLA} = \frac{746 \, \text{hp}}{\sqrt{3} \, V \, \eta \, \text{PF}} $$
Single-phase:
$$ \text{FLA} = \frac{746 \, \text{hp}}{V \, \eta \, \text{PF}} $$
Locked-rotor (starting current, NEMA Code G–H):
$$ \text{LRA} \approx 6 \times \text{FLA} \quad (\text{NEMA Design B, typical}) $$
746 watts per horsepower · η motor mechanical-to-electrical efficiency · PF motor power factor at rated load · FLA full-load amps at rated voltage and load.

NEC tabulated FLA — what it's for

NEC Table 430.250 gives standard FLA values for three-phase induction motors. These are CONSERVATIVE — they assume η × PF = 0.85 for < 5 hp and 0.92 for 100+ hp, neither of which exactly matches a specific nameplate. NEC 430.6(A)(1) requires use of the tabulated value for branch circuit and motor disconnect sizing, not the actual nameplate FLA.

The reason: protective device sizing must accommodate any motor of the given size, not just the specific motor purchased. If a more efficient motor is later substituted, the original wire and breaker must still handle it.

Why FLA isn't the design current

Conductor ampacity per NEC 430.22 = 125% × FLA (for continuous operation). OCPD per NEC 430.52: 250% × FLA for thermal-magnetic breakers, 175% for non-time-delay fuses, 300% × FLA for time-delay fuses.

Why the multipliers? Two reasons:

Locked-rotor current

At startup, before the rotor accelerates, the motor draws locked-rotor amps (LRA), typically 5.5–6.5× FLA for NEMA Design B. NEMA design code letters indicate LRA range:

Reduced-voltage starters (autotransformer, soft-starter, VFD) cut LRA to 30–60% of full-voltage starting, reducing voltage dips and mechanical shock.

Service factor (SF) overload allowance

Standard motors have SF = 1.15, meaning they can run at 115% of rated load continuously without damage. NEC 430.32 sets motor overload protection at 125% × FLA for SF ≥ 1.15, or 115% × FLA for SF = 1.0. Don't use the SF rating to sustain operation — it's an emergency margin, not a design point.

Reference: National Electrical Code (NFPA 70-2023), Article 430. NEMA MG-1: Motors and Generators. IEEE Std 141 (Red Book).

Related tools

Monthly engineering case studies

One real stormwater or hydraulics design problem per month, with the math worked out and the gotchas called out. No tutorials, no fluff.

Free. Unsubscribe anytime. Privacy.

Engineer of Record — Stamp & Signature
APPLY PE STAMP HERE
Engineer Name
License No.
State
Signature
Date
Project / Sheet
By stamping and signing, the Engineer of Record certifies that the inputs, formulas, and applicability of this calculation have been reviewed for the specific design context. PE-Calc tools provide computational support only — the engineer is responsible for verifying results, applying engineering judgment, and complying with applicable codes and standards.
Calculation generated at pe-calc.com