All tools

Hazen-Williams — 12-inch Steel Water Main Worked Example

Friction loss for a welded steel transmission main between a booster station and an elevated tank. Steel is the material where the C-factor story matters most: new lined steel starts near C = 140–145, but unlined or aging steel tuberculates its way down toward C = 100 and below — and head loss climbs steeply as it does. Sources: Hazen & Williams, Hydraulic Tables; AWWA M11, Steel Pipe — A Guide for Design and Installation.

The main

Pipe12-inch welded steel, cement-mortar lined, d = 12 in
Length L3,500 ft
Design flow Q1,500 gpm
C-factor (design)130 (lined steel, mid-life; see C reference)
Step 1 · Velocity check first

Is 1,500 gpm reasonable in a 12-inch main?

Q = 1,500 gpm ÷ 448.8 = 3.34 cfs
A = π/4 · (1.0 ft)² = 0.785 ft²
V = 3.34/0.785 = 4.3 ft/s — comfortably inside the 2–6 ft/s transmission range ✓

Above ~6–7 ft/s, surge pressures and per-foot losses climb quickly in transmission service; below ~2 ft/s the pipe is oversized for the duty (capital tied up, water age grows).

Step 2 · Hazen-Williams friction loss

The design-condition number

hf = 10.44 · L · Q1.852 / (C1.852 · d4.87)   [Q gpm, d in, L, hf ft]

Q1.852 = 15001.852 = 7.62 × 105
C1.852 = 1301.852 = 8.22 × 103
d4.87 = 124.87 = 1.81 × 105

hf = 10.44 · 3500 · 7.62×105 / (8.22×103 · 1.81×105)
hf = 2.79×1010 / 1.49×109 = 18.8 ft  (≈ 5.4 ft per 1,000 ft)

In pressure terms: 18.8 ft ÷ 2.31 ft/psi = 8.1 psi
Step 3 · Aging sensitivity

The same main across its service life

ConditionChf (ft)Loss vs design
New, cement-mortar lined14016.3−13%
Design (mid-life lined)13018.8
Unlined / tuberculated, decades old10030.5+62%
Scaling shortcut: hf ∝ (1/C)1.852
  hf,100 = 18.8 · (130/100)1.852 = 18.8 · 1.626 = 30.5 ft
Design both directions. For pump head and fire-flow adequacy, the low-C (aged) case governs — can the system still deliver at C = 100? For surge and velocity checks, the high-C (new) case governs — flows run highest when the pipe is smoothest. One C-factor cannot be conservative for both questions.
Step 4 · What Hazen-Williams quietly assumes

Limits of the equation

Tools used in this example

Reproduce every step: Hazen-Williams tool with C from the C-factor card, then total dynamic head and pump BHP to finish the pumping picture. Companion example: 6-inch PVC distribution main.

Get future worked examples in your inbox

One real stormwater or hydraulics design problem per month, with the math worked out and the gotchas called out. Free.

Free. Unsubscribe anytime. Privacy.