All tools Print with PE stamp box Designed for sealed engineering submittals — print drops PE stamp + signature block at the end.

Transformer kVA Sizing

Distribution-transformer sizing from connected load. Applies a demand factor (load is rarely at 100% simultaneously) and a future-growth allowance, then rounds up to the next standard kVA size. Reports primary and secondary full-load amps for switchgear sizing.

kW
— (typical 0.80–0.95)
— (NEC 220 by occupancy)
% (typical 20–30%)
V (utility primary; common 4160, 13.2k, 13.8k)
V (208, 240, 480 typical)
kVA
kVA
kVA
A
A

Defaults: 500 kW connected, PF = 0.85, DF = 0.80, 25% growth, 13.8 kV primary to 480V secondary — typical industrial substation. Standard kVA sizes: 15, 30, 45, 75, 112.5, 150, 225, 300, 500, 750, 1000, 1500, 2000, 2500, 3000, 5000.

Required kVA:
$$ \text{kVA}_{req} = \frac{P \cdot \text{DF}}{\text{PF}} \cdot (1 + \text{growth}) $$
Round up to next standard kVA size.
Primary and secondary current (3-ph):
$$ I_p = \frac{\text{kVA} \cdot 1000}{\sqrt{3} \, V_p}, \qquad I_s = \frac{\text{kVA} \cdot 1000}{\sqrt{3} \, V_s} $$
Demand factor (DF) ratio of peak demand to total connected load · Growth spare capacity for future loads · standard sizes follow ANSI C57.12.10.

Demand factors — NEC 220

Demand factor accounts for the fact that not every load operates simultaneously at full output. NEC Article 220 specifies factors by occupancy:

Use Table 220.42, .54, .55, .56 for specific occupancies. Industrial loads often run at 1.0 because the connected load IS the operating load.

Growth allowance

Standard practice: 20–30% future growth on commercial/industrial transformers. For data centers or rapidly growing campuses, 50–100%. The cost difference between a 1500 kVA and 2000 kVA transformer is small, and adding capacity later is expensive. Specify utility-coordination at the highest growth tier you can financially justify.

Standard kVA sizes (ANSI C57.12.10)

Always round up to the next standard size. Custom sizes are available but cost 30–50% more for the manufacturer to build.

Loading guidelines

Continuous loading at > 100% rated kVA shortens transformer life. ANSI C57.91 allows brief overloading per the loading guide:

Standard practice: design at 80% of nameplate rated kVA. The 25% growth allowance + 80% loading gives 25% × 1.25 = 56% spare capacity at design point.

Primary and secondary current

I = kVA × 1000 / (√3 × V) for three-phase. The primary current at 13.8 kV is small (1500 kVA / (1.73 × 13800) = 63 A) — easy to switchgear. The secondary at 480V is much larger (1804 A) and requires substantial bus, breakers, and ground-fault protection.

Reference: National Electrical Code (NFPA 70-2023), Article 220 and 450. ANSI C57.12.00 / C57.12.10. IEEE Std 141 (Red Book).

Related tools

Monthly engineering case studies

One real stormwater or hydraulics design problem per month, with the math worked out and the gotchas called out. No tutorials, no fluff.

Free. Unsubscribe anytime. Privacy.

Engineer of Record — Stamp & Signature
APPLY PE STAMP HERE
Engineer Name
License No.
State
Signature
Date
Project / Sheet
By stamping and signing, the Engineer of Record certifies that the inputs, formulas, and applicability of this calculation have been reviewed for the specific design context. PE-Calc tools provide computational support only — the engineer is responsible for verifying results, applying engineering judgment, and complying with applicable codes and standards.
Calculation generated at pe-calc.com