Structural analysis

How to Analyze a Roof Truss — Step-by-Step with the Free Truss Calculator

By Michael Flynn, PE · water resources & dam safety engineer ·

A practical walkthrough of the free truss calculator: choosing the type, putting loads where they belong, picking combinations, setting bracing, and reading the results like a reviewer. Each step names the mistake it prevents.

Steps
  1. Pick the truss type and geometry
  2. Enter loads as pressures on plan
  3. Choose ASD or LRFD combinations
  4. Choose the member check and sizes
  5. Set bracing to match the building
  6. Read the results
  7. Edit joints and members for anything non-standard
  8. Know what the tool does not do
Step 1

Pick the truss type and geometry

Pitched roof trusses: Fink (W), king post, queen post, Howe and Pratt roof (choose the panel count), scissor (with a separate bottom-chord pitch) and mono-pitch. Parallel-chord trusses (Pratt, Howe, Warren, Warren with verticals) take a depth and a panel count instead of a pitch. Spans are measured between bearings, and pitch is in inches of rise per 12 in of run.

Which type? As a rough guide (manufacturers' ranges vary): king post for short spans, Fink and queen post for typical residential spans, and Howe or Pratt roof patterns with more panels as spans grow and panel lengths need to stay short. The coefficient card compares force levels across types and pitches at a glance.
Step 2

Enter loads as pressures on the horizontal projection

Enter TCDL, TCLL, BCDL and BCLL in psf on plan, plus the truss spacing. The calculator multiplies pressure by spacing and tributary length and lumps the result at the panel points. Loads at the heels go directly into the bearings. Set "TCLL is" to snow, roof live or floor live: that sets the load-duration factor in wood and the combination factors.

Sloped vs plan dead load. Roofing weight is often quoted per square foot of roof surface. On a 6/12 roof, 10 psf of surface is 10 / cosθ = 11.2 psf on plan. Convert it before you enter TCDL. Snow and roof live loads in ASCE 7 are already on the horizontal projection.

Wind is entered as a net uplift pressure on the top chord, the case that reverses member forces. It is not a full wind-pressure model: inward pressure on the windward slope and drag on the truss are not included. Member self-weight is optional; for light wood trusses it is usually already part of TCDL and BCDL.

Step 3

Choose ASD or LRFD combinations

ASD runs D, D + L, D + 0.6W and 0.6D + 0.6W (ASCE 7 §2.4). LRFD runs 1.4D, 1.2D + 1.6L, 1.2D + 1.0W + 0.5L and 0.9D + 1.0W (§2.3). Each member is checked under every combination, and the governing one is reported. Wood design uses ASD (NDS), and each ASD combination carries its own CD. That is why dead load alone can govern; see the Fink example, step 5.

Step 4

Choose the member check and sizes

Step 5

Set bracing to match the building

MemberOptionsTypical
Top chordContinuous (sheathing / purlins) · panel points onlyContinuous: sheathing nailed to the chord
Bottom chordContinuous (ceiling) · panel points onlyContinuous under a drywall ceiling; panel points in garages and storage buildings
WebsPanel points only · lateral restraint at mid-length (CLR)Panel points, plus a CLR on long compression webs

Bracing sets the out-of-plane buckling length, about the 1.5 in face of a 2x member. When a compression member's le/d exceeds 50, the NDS doesn't allow it, and the calculator reports the violation instead of a ratio. The uplift example shows how a bottom chord with no ceiling, and long webs under uplift, trip this limit.

Step 6

Read the results like a reviewer

  1. Stability line. It should read "Stable" and say whether the truss is determinate (m + r = 2j). A mechanism means a missing member or support; the calculator names the joint.
  2. Total vertical load. Check it against your own (pressure × spacing × span) before you look at anything else.
  3. Member table. Each member's service force, its maximum tension and compression with the combination that causes each, and the demand/capacity ratio with the governing check. Switch the diagram between forces, D/C ratio, deflection and loads.
  4. Deflection. Total and live, as span/Δ, against the limits you set. These are pin-jointed elastic values; metal-plate trusses deflect more in service (joint slip, creep).
  5. Reactions. Maximum down and maximum uplift per bearing, for the wall, the girder or the uplift connector.
Step 7

Edit joints and members for anything non-standard

Every template opens into editable joint, member and point-load tables. Add a hip girder's concentrated load, an attic room, a cantilevered heel or an extra web, then set the template to "Custom — keep my edited geometry" so your changes stay. Export the member forces as CSV, or copy a share link that reproduces the whole model for a reviewer.

Step 8

Know what the tool does not do

Pre-engineered trusses are designed by the truss manufacturer's engineer. Use this tool to size a site-built truss, check a truss design, plan a repair or a modification, or learn how the forces flow.

Worked examples

Fink roof truss, NDS check · Wind uplift and bracing · Pratt footbridge, method of sections

Frequently asked questions

How do you calculate the loads on a roof truss?

Multiply each pressure (dead, snow or roof live, measured on the horizontal projection) by the truss spacing to get a line load in plf, then lump it at the panel points by tributary length: half the panel on each side of a joint. Top-chord loads go to the top joints, ceiling loads to the bottom joints, and the half-panels at the heels go directly into the bearings.

Is a roof truss determinate?

Most standard roof trusses (king post, queen post, Fink, Howe, Pratt) are statically determinate: members plus reaction components equals twice the number of joints. That means the member forces depend only on the loads and geometry, not on the member sizes. Adding redundant members or a third bearing makes the truss indeterminate, and the stiffness method is needed.

Can I use this instead of truss design software?

For site-built trusses, checks, repairs and teaching, yes, within its limits: pinned joints, simple-span chord bending, net-uplift wind only and no connector plate design. Pre-engineered metal-plate-connected trusses are designed to ANSI/TPI 1 by the manufacturer's engineer.